Performance of Displacement Ventilation for Hospital Patient Rooms with Varying Cooling Loads

ASHRAE Annual Conference, Kansas City, KS, 2019

Author:

Kishor Khankari

Abstract:

A CFD analysis of a displacement ventilation system for reduced cooling load conditions is performed using the previously developed CFD model of a hospital patient room. The previous analysis was performed for design (high) cooling load conditions. In this study the effect of supply air flow rate and supply air temperature on the performance of HVAC system is evaluated. As expected the previous levels of high airflow rate with low supply air temperature, which were suitable for the high load conditions, would make the occupants feel too cold under the reduced cooling load. This analysis indicates reducing the airflow rate and also at the same time increasing the supply air temperature would make occupants feel warm and the stratified layer of the hot air could descend too close to the occupied zone. The operating conditions of high supply airflow rate with increased supply air temperature and reduced airflow rate with reduced supply air temperature show promise of creating reasonable level of thermal comfort in the occupied zone. However, the operating conditions of the latter case would require less fan and thermal energy to provide similar level of thermal comfort. These conditions would also keep the stratified thermal layer close to the ceiling away from the occupied zone. This analysis further indicates under the reduced supply airflow rate (2 ACH), instead of the room exhaust, the bathroom exhaust through the bathroom door opening would dominate the flow path of the exit air and the resulting flow path of the airborne particles. The supply air flow rate of 2 ACH does not meet the minimum requirement of ASHRAE/ASHE Standard 170-2017 of 6 ACH for the occupied zone for displacement ventilation.

Fill the following form to download






    About the author

    Dr. Kishor Khankari

    ASHRAE Fellow, ASHRAE Distinguished Lecturer

    Dr Kishor Khankari is the founder of AnSight LLC. As a specialist in Computational Fluid Dynamics (CFD), his passion for solving engineering problems and providing sound scientific solutions has led to innovations and optimized designs in the industry.

    A noted expert in his field, he has a Ph.D. from the University of Minnesota and has published in several technical journals and trade magazines. As a well sought-after speaker Dr. Khankari makes regular presentations in various technical conferences and professional meetings worldwide.

    Recent Posts

    Ventilation Guidance for Residential Kitchen with Gas Stove

    Recently the residential gas stoves were in the News due to the generation of pollutants during their operation. Cooking activities as well as the combustion of natural gas through gas stove burners produce several indoor pollutants. Exhausting these pollutants from...

    CFD Analysis of Residential Kitchen Ventilation with Gas Stove

    Proper ventilation of the kitchen is essential to reduce the occupant exposure to various pollutants generated during the cooking and the combustion of natural gas through the gas stove burners. Several parameters related to the design and operation can affect the...

    CFD Analysis of Demand Control Ventilation for Laboratories

    What is Demand Control Ventilation (DCV)? Often high air change rates per hour (ACH) are specified for laboratories to meet the goal of ventilation. The ACH numbers specified are mostly consensuses based on simplistic approaches of perfect mixing of contaminants with...

    CFD Analysis Evaluates Efficacy of Reactive Air Cleaning Technology

    What is reactive air cleaning? Reactive air cleaning involves the release of reactive agents in the room to actively mitigate airborne pathogens and other pollutants. Unlike traditional dilution ventilation in which the concentration of the airborne pathogens in the...