Operational Guidance For Residential Kitchen Ventilation With A Gas Stove

ASHRAE Journal, Vol. 67, no. 2, February 2025

Author:

Kishor Khankari

Abstract:

Cooking activities and the use of gas stoves can produce indoor pollutants in homes. These pollutants can be harmful to people depending on their exposure levels. Using kitchen ventilation with range hoods or over-the-range microwaves (OTR) can help reduce occupant exposure. However, the effectiveness of the ventilation system depends on factors such as its design, installation, and how it is used.

This study with the help of a mass balance approach evaluates the impact of various parameters on the transient well-mixed concentration of Nitrogen Dioxide (NO2) and resulting occupant exposure. These factors include the exhaust air flow rate, the delay in starting the exhaust fan after starting the burner, the duration for which the exhaust fan is left operating after the burner is turned off, and the size of the kitchen. These analyses were performed systematically by varying a single parameter at a time and developed practical guidelines for the operation of a kitchen ventilation system.

The study suggests that in order to keep the exposure of NO2 below the acceptable level of 90 parts per billion-hour (ppb-hr):

  • Kitchens should have an exhaust flow rate of at least 100 cfm (47 L/s).
  • The exhaust fan should be started within ten minutes of starting the burners (while cooking).
  • The exhaust fan should be kept on for at least five minutes after turning the burner off (after cooking).
  • Exceeding the above parameters would help further reduce both short-term (acute) and long-term (chronic) exposures to pollutants.

Fill the following form to download






    About the author

    Dr. Kishor Khankari

    ASHRAE Fellow, ASHRAE Distinguished Lecturer

    Dr Kishor Khankari is the founder of AnSight LLC. As a specialist in Computational Fluid Dynamics (CFD), his passion for solving engineering problems and providing sound scientific solutions has led to innovations and optimized designs in the industry.

    A noted expert in his field, he has a Ph.D. from the University of Minnesota and has published in several technical journals and trade magazines. As a well sought-after speaker Dr. Khankari makes regular presentations in various technical conferences and professional meetings worldwide.

    Recent Posts

    Ventilation Guidance for Residential Kitchen with Gas Stove

    Recently the residential gas stoves were in the News due to the generation of pollutants during their operation. Cooking activities as well as the combustion of natural gas through gas stove burners produce several indoor pollutants. Exhausting these pollutants from...

    CFD Analysis of Residential Kitchen Ventilation with Gas Stove

    Proper ventilation of the kitchen is essential to reduce the occupant exposure to various pollutants generated during the cooking and the combustion of natural gas through the gas stove burners. Several parameters related to the design and operation can affect the...

    CFD Analysis of Demand Control Ventilation for Laboratories

    What is Demand Control Ventilation (DCV)? Often high air change rates per hour (ACH) are specified for laboratories to meet the goal of ventilation. The ACH numbers specified are mostly consensuses based on simplistic approaches of perfect mixing of contaminants with...