CFD Analysis of Enclosed Parking Garage Ventilation

ASHRAE Winter Virtual Conference, 2021

Author:

Dr. Kishor Khankari

Abstract:

The purpose of an enclosed parking garage ventilation system is to create a safe environment for the occupants by diluting concentration levels of hazardous contaminants such as carbon monoxide (CO) to a certain acceptable level. The effectiveness of a ductless ventilation system for enclosed parking garages depends on several factors such as the makeup airflow rate, number and locations of exhaust points, and number and locations of makeup air points. With the help of Computational Fluid Dynamics (CFD) analyses, this study systematically evaluates the impact of three different HVAC configurations on the airflow patterns, distribution of CO concentration, and on Spread Index – a newly developed measure of ventilation effectiveness. The HVAC configuration with a single makeup air opening with a single exhaust the makeup air gets contaminated along its path and form air recirculation zones with high CO concentration. When additional makeup air points are introduced with a single exhaust point a part of the makeup air short-circuited through the exhaust point without passing through the sources of contaminant. As a result, the average CO concentration in the breathing zone increased with a significant reduction in ventilation effectiveness. The ventilation performance significantly improved with the reduction in the CO concentration levels with the distributed makeup air and exhaust points at several strategic locations. Such high ventilation effectiveness can be achieved even at lower ventilation rates. These studies demonstrate that CFD analyses can help in identifying the potential issues with the makeup air distribution in a space and can provide valuable insights in developing appropriate mitigation strategies to create a safe environment in the enclosed parking garages.

Fill the following form to download






    About the author

    Dr. Kishor Khankari

    ASHRAE Fellow, ASHRAE Distinguished Lecturer

    Dr Kishor Khankari is the founder of AnSight LLC. As a specialist in Computational Fluid Dynamics (CFD), his passion for solving engineering problems and providing sound scientific solutions has led to innovations and optimized designs in the industry.

    A noted expert in his field, he has a Ph.D. from the University of Minnesota and has published in several technical journals and trade magazines. As a well sought-after speaker Dr. Khankari makes regular presentations in various technical conferences and professional meetings worldwide.

    Recent Posts

    Ventilation Guidance for Residential Kitchen with Gas Stove

    Recently the residential gas stoves were in the News due to the generation of pollutants during their operation. Cooking activities as well as the combustion of natural gas through gas stove burners produce several indoor pollutants. Exhausting these pollutants from...

    CFD Analysis of Residential Kitchen Ventilation with Gas Stove

    Proper ventilation of the kitchen is essential to reduce the occupant exposure to various pollutants generated during the cooking and the combustion of natural gas through the gas stove burners. Several parameters related to the design and operation can affect the...

    CFD Analysis of Demand Control Ventilation for Laboratories

    What is Demand Control Ventilation (DCV)? Often high air change rates per hour (ACH) are specified for laboratories to meet the goal of ventilation. The ACH numbers specified are mostly consensuses based on simplistic approaches of perfect mixing of contaminants with...

    CFD Analysis Evaluates Efficacy of Reactive Air Cleaning Technology

    What is reactive air cleaning? Reactive air cleaning involves the release of reactive agents in the room to actively mitigate airborne pathogens and other pollutants. Unlike traditional dilution ventilation in which the concentration of the airborne pathogens in the...