Analysis of Airflow Patterns and Air Temperature Distribution Surrounding Air Cooled Chillers

ASHRAE Annual Conference, Atlanta, GA, 2015

Author:

Kishor Khankari

Abstract:

Air-cooled chillers are becoming a primary choice for heat rejection in the regions of the short supply of water. The performance of the air cooled condensers/chillers can degrade under high ambient temperature and windy conditions. Several factors including the wind speed, wind direction, spacing between the chillers, and distance from the adjacent building can affect the performance of air-cooled chillers. This study with the help of Computational Fluid Dynamics (CFD) analyses evaluates the impact of these parameters on the airflow patterns, dispersion of the hot exhaust plumes from the chillers, and on the air temperature distribution at chiller air intakes. The extent of hot exhaust plume recirculation into the chillers intakes is estimated in terms of the average intake air temperature. These analyses indicate increasing wind speeds increase the recirculation of exhaust plumes into the chiller air intakes. Orienting the chillers perpendicular to the prevailing wind direction can promote the cascading effect of the hot plume recirculation. The spacing between the chillers has a larger impact on the recirculation of hot exhaust plumes than the distance between the building and the chillers. Reducing the spacing between the chillers can significantly increase the recirculation of hot exhaust plumes and resulting intake air temperature. This study further indicates that placing the chillers too close to the building can promote the recirculation of hot plumes back into the chiller air intakes. However, moving the chillers beyond a certain distance from the adjacent building would not yield any significant reduction in the intake air temperatures.

Fill the following form to download






    About the author

    Dr. Kishor Khankari

    ASHRAE Fellow, ASHRAE Distinguished Lecturer

    Dr Kishor Khankari is the founder of AnSight LLC. As a specialist in Computational Fluid Dynamics (CFD), his passion for solving engineering problems and providing sound scientific solutions has led to innovations and optimized designs in the industry.

    A noted expert in his field, he has a Ph.D. from the University of Minnesota and has published in several technical journals and trade magazines. As a well sought-after speaker Dr. Khankari makes regular presentations in various technical conferences and professional meetings worldwide.

    Recent Posts

    Aerodynamic Containment Can Reduce Spread of Infectious Aerosols

    Building Ventilation and Airborne Transmission of Infectious Aerosols Air is the primary carrier of heat, moisture, and airborne contaminants including infectious aerosols in indoor spaces. The primary goal of building ventilation is to create a healthy environment...

    Can Space Volume Adversely Affect the Dilution of Contaminants?

    What is Air Changes per Hour (ACH)? Clean air is supplied to indoor spaces to dilute the concentration of contaminants to a certain acceptable level. The requirement for such ventilation airflow rate is generally specified in terms of Air Changes per Hour (ACH). It is...