(734) 327 4079 info@ansight.com
AnSight’s Solutions for COVID-19

Analysis of Airflow Distribution and Contaminant Flow Path in the Hospital Operating Room

ASHRAE Winter Conference, Las Vegas, NV, 2017

Author:

Kishor Khankari

Abstract:

A probable factor in minimizing the infection due to airborne bacteria in the hospital operating room is to minimize the entrainment of air from the non-sterile zone into the sterile zone. A Computational Fluid Dynamics (CFD) model of a virtual hospital operating room is developed to analyze the impact of supply airflow rates or ACH on the airflow patterns, temperature distribution, and on the resulting flow path of airborne particulates. These analyses indicate the supply airflow rate, and hence, the discharge velocity of the unidirectional air jet, has a little impact on the overall airflow patterns and the thermal stratification in non-sterile zone occurs at all levels of supply airflow rates. Increasing the supply airflow rate and associated heat capacity of the supply air helps in reducing thermal gradients between the sterile and non-sterile zones which in turn may reduce the entrainment of the air from the non-sterile zone into the sterile zone. Increasing the supply airflow rate can also significantly reduce relative acceleration of the centerline velocity – an indication of the reduction in the entrainment. This study further indicates the supply airflow rate has a little impact on the overall flow path of airborne particulates. When these particulates are originated within a sterile zone they are generally swept away into the non-sterile zone where they can recirculate without significant re-entrainment before exiting the operating room. However, when these particulates originate from the non-sterile zone, irrespective of the supply airflow rate, they get entrained into the sterile zone. The flow of path of these particulates may need to be altered in order to avoid such entrainment. This can be achieved only by significantly altering the airflow patterns in the non-sterile zone. The legacy HVAC design for hospital operating rooms involving a ceiling array of laminar supply diffusers and low wall exhaust grills on the opposite walls may require further evaluation.

Fill the following form to download






    About the author

    Dr. Kishor Khankari

    ASHRAE Fellow, ASHRAE Distinguished Lecturer

    Dr Kishor Khankari is the founder of AnSight LLC. As a specialist in Computational Fluid Dynamics (CFD), his passion for solving engineering problems and providing sound scientific solutions has led to innovations and optimized designs in the industry.

    A noted expert in his field, he has a Ph.D. from the University of Minnesota and has published in several technical journals and trade magazines. As a well sought-after speaker Dr. Khankari makes regular presentations in various technical conferences and professional meetings worldwide.

    Recent Posts

    CFD Analysis of Demand Control Ventilation for Laboratories

    What is Demand Control Ventilation (DCV)? Often high air change rates per hour (ACH) are specified for laboratories to meet the goal of ventilation. The ACH numbers specified are mostly consensuses based on simplistic approaches of perfect mixing of contaminants with...

    CFD Analysis Evaluates Efficacy of Reactive Air Cleaning Technology

    What is reactive air cleaning? Reactive air cleaning involves the release of reactive agents in the room to actively mitigate airborne pathogens and other pollutants. Unlike traditional dilution ventilation in which the concentration of the airborne pathogens in the...

    Can Indoor Airflow Patterns Affect the Upper-Room UVGI Performance?

    What is Ultraviolet Germicidal Irradiation (UVGI) (UV-C)? Upper-room Ultraviolet Germicidal Irradiation (UVGI) involves the use of UVC to inactivate airborne pathogens. Wall or ceiling-mounted UVC fixtures are placed near the ceiling to generate a UVC field at 254 nm...