Analysis of Spread Index: A Measure of Laboratory Ventilation Effectiveness

ASHRAE Annual Conference, Houston, TX, 2018

Author:

Kishor Khankari

Abstract:

A laboratory ventilation system should limit the spread of contaminants and quickly purge the chemicals from a lab space to bring the concentrations at or below certain acceptable level. This study with the help of transient isothermal Computational Fluid Dynamics (CFD) analysis evaluates effectiveness of a laboratory ventilation system using two measures, namely, Spread Index (SI)TC and Purge Time (PT)TC. (SI)TC quantifies how much of the lab volume is covered by an unacceptable level of concentration which is presumably the high risk concentration threshold (TC). Whereas (PT) TC evaluates how much time it would take to purge the contaminants from the lab space to bring those concentration levels at or below the acceptable limit. The practical use of these indices are demonstrated by comparing the performance of two ventilation systems with two and three exhaust grills configurations. These analyses show (SI)TC increases with the release of chemicals and reaches its peak until the release is stopped whereas (PT)TC depends on the nature of the spread of contaminants. This analysis showed the distributed exhaust strategy with three exhaust grills significantly reduced the (SI)TC values resulting in reduced concentration levels and chemical exposure (dose) of occupants. This study further indicates in spite of the well mixed airflow patterns the contaminant distribution especially in the breathing zone of the occupants is highly non-uniform. Interestingly the occupant closer to the exhaust grills shows high level of exposure than the one closer to the contaminant source. Therefore, control of lab environment by monitoring the concentration levels in the exhaust duct can compromise the safety of some occupants by under predicting their chemical exposure (dose).

Fill the following form to download






    About the author

    Dr. Kishor Khankari

    ASHRAE Fellow, ASHRAE Distinguished Lecturer

    Dr Kishor Khankari is the founder of AnSight LLC. As a specialist in Computational Fluid Dynamics (CFD), his passion for solving engineering problems and providing sound scientific solutions has led to innovations and optimized designs in the industry.

    A noted expert in his field, he has a Ph.D. from the University of Minnesota and has published in several technical journals and trade magazines. As a well sought-after speaker Dr. Khankari makes regular presentations in various technical conferences and professional meetings worldwide.

    Recent Posts

    Ventilation Guidance for Residential Kitchen with Gas Stove

    Recently the residential gas stoves were in the News due to the generation of pollutants during their operation. Cooking activities as well as the combustion of natural gas through gas stove burners produce several indoor pollutants. Exhausting these pollutants from...

    CFD Analysis of Residential Kitchen Ventilation with Gas Stove

    Proper ventilation of the kitchen is essential to reduce the occupant exposure to various pollutants generated during the cooking and the combustion of natural gas through the gas stove burners. Several parameters related to the design and operation can affect the...

    CFD Analysis of Demand Control Ventilation for Laboratories

    What is Demand Control Ventilation (DCV)? Often high air change rates per hour (ACH) are specified for laboratories to meet the goal of ventilation. The ACH numbers specified are mostly consensuses based on simplistic approaches of perfect mixing of contaminants with...

    CFD Analysis Evaluates Efficacy of Reactive Air Cleaning Technology

    What is reactive air cleaning? Reactive air cleaning involves the release of reactive agents in the room to actively mitigate airborne pathogens and other pollutants. Unlike traditional dilution ventilation in which the concentration of the airborne pathogens in the...